Compare

Voltrus SCADA vs Ignition

Ignition is the reference for modern SCADA, with a big module catalogue and integrator network. Voltrus SCADA is a single open-source binary for smaller sites and integrators who want a free Core and a flat per-site licence. Here is how the published prices and limits line up.

Competitor facts are from their own pages, read on 17 November 2026. Numbers in the table link to the sources.

Voltrus SCADA and Ignition, point by point.

Factor
Voltrus SCADA
Ignition
Free option for real projects
Core is free for commercial use under AGPL-3.0, with no device, tag, retention or time limits and no licence key.
An unlicensed gateway runs 2 hours at a time; the trial can be reset any number of times. Maker Edition is free for personal, non-commercial use only (10,000 tags, 10 sessions).[1],[3],[6]
Licensed site, entry price
Integrator: $249 lifetime per site, or $19 per site per month. Enterprise: $999 lifetime, or $79 per month.
Ignition Platform $1,200, plus modules: Perspective $11,225, Vision $8,330, Reporting $3,900, SQL Bridge $2,300 (list prices for a single licence). The Application Building suite (Perspective + Reporting) is $13,500.[2],[4],[7]
Historian
Built into Core: compressed blocks in SQLite, hourly and daily tiers, trends and CSV/Excel export.
Industrial Historian suite (Historian Core, SQL Historian): $3,500.[4],[6]
Alarm notifications
Email, webhook and push in Core. Telegram alarms and a mobile app in Integrator.
Alarm Notification module $2,245. Alarm Management suite (adds SMS, Twilio and voice) $3,200.[2],[4],[6]
Edge devices
The same binary runs on a Raspberry Pi (Linux aarch64 build). No separate edge edition.
Ignition Edge Panel $1,950, Edge IIoT $945. Edge allows at most two concurrent client views and 35 days of internal data storage.[2],[4],[6]
Support and upgrades
Lifetime keys do not expire. If a monthly key lapses, Enterprise features keep working for 7 days, then the install falls back to Core, which never stops.
Support plans cost 16%, 20% or 24% of the software retail price per year. Without a plan, a major upgrade costs 65% of the current retail price.[4],[7]
What you install
One executable with the web UI inside. It creates its SQLite database on first start.
A Java-based gateway; the installer ships its own Java runtime.[5],[6]
AI agents
Built-in MCP server at /mcp: Claude and other MCP clients read values and acknowledge alarms, with confirmed writes and a read-only switch.
Not covered by the pages we read.[6]

List prices in the vendor's currency, as published (the source says whether tax is included), before any discount a distributor may give. Partner and reseller figures are indications, not vendor quotes. If a number here is out of date, tell us at support@voltrus.id and we will fix it.

What each one costs an engineer's laptop.

The same water-treatment plant (47 Modbus tags polled every second) on five platforms, idle with no client open, on one Linux machine, 24–25 Nov 2026. Tested in our lab, 24–25 Nov 2026

Measured Voltrus SCADA0.52.0FUXA1.3.6Rapid SCADA6.5.1Ignition8.3.10WinCC OA3.21
Download 22.5 MB tarball936 MB image139 MB zip + .NET 10 runtime2.11 GB compressed imageSiemens packages, image built locally
On disk 63 MB binary (web UI and drivers inside)936 MB image616 MB image4.45 GB image + 1.2 GB Designer on the engineer's PC8.02 GB image
Processes 11 (Node.js)4 (.NET services)1 JVM (+ wrapper)13 WinCC OA + 11 PostgreSQL
Idle RAM, no client 14–16 MiB81 MiB191–211 MiB880–890 MiB235–372 MiB
Idle CPU, % of one core 0.3–0.4 %~0.8 %1.7–2.5 %44–59 %15–21 %
Start to usable 0.1–0.6 s10 s~10 s48–75 s20 s to the first value

Three Voltrus plants side by side, each with its own simulator, config, SQLite database and port, from one copy of the binary: 44 MiB of RAM and about 1 % of one core in total; 63 MB binary plus 24.5 MB of data after about 70 minutes.

  • One Ignition gateway can host several projects: devices, tag providers and historians are shared, so three plants in one gateway cost roughly one gateway plus their tags. Separate gateways (other versions, modules or customers) are a JVM each. From the Ignition docs; the per-gateway cost is from our lab.
  • The Ignition and WinCC OA figures were taken before the lab machine started swapping. Ignition's idle CPU was 44–49 % about 15 minutes after start and 59 % after 21 minutes; it may settle lower after longer.
  • Not measured: several copies of FUXA, Rapid SCADA, Ignition or WinCC OA at once, RAM with clients connected, Windows and macOS, battery and fan.
  • Method, caveats and the scripts to repeat it

What Ignition does better.

We built the same plant in Ignition 8.3.10 in trial mode, through its REST API and project files, then opened it in the Designer. It works well. It is also the heaviest platform we ran on a laptop.

  • UDTs: a Pump type with parameters bound into the OPC item paths, the trip alarm defined once in the type, and per-instance overrides. The alarm fired on the right pump.
    Tested in our lab, 24–25 Nov 2026
  • One Pump view with a single tagPath parameter served three pumps, writes included. That is the cleanest "one faceplate, many pumps" pattern we saw.
    Tested in our lab, 24–25 Nov 2026
  • Power Chart: three pens from the historian with min, max and average per pen, zoom and pan, with no setup beyond the pens.
    Tested in our lab, 24–25 Nov 2026
  • Views are JSON files: hand-written view files loaded after a file scan, without the Designer, and worked the first time.
    Tested in our lab, 24–25 Nov 2026
  • One gateway hosts many projects; redundant gateways, the Gateway Network and a large module catalogue with many certified integrators.
    From vendor documentation
  • The Designer merges other engineers' changes and opens a conflict screen on save.
    From vendor documentation

Lessons we shipped.

Each of these came out of the lab. They shipped in Voltrus SCADA v0.53.0 (25 Nov 2026). Details, commits and tests: lessons implemented.

  • Tag-swap faceplates: one pump, motor, valve or analog faceplate definition, opened by many symbols, each with its own tags; commands go through the command queue. Not yet: live-linked equipment types like UDTs.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • Screens made over REST or MCP open in the editor and save back identically (tested).
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • A trend popup from any value, up to six pens, each with its own autoscaled axis.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026
  • An official Dockerfile with a CI build (103 MB image, about 29 MiB idle in a smaller scenario); no registry image yet.
    Shipped in v0.53.0; lesson from our lab, 24–25 Nov 2026

Each one is the right call somewhere.

Pick Voltrus SCADA when

  • The site has fewer than a few thousand tags and the budget will not stretch to a module stack.
  • You are an integrator and want one flat price per site, or a free Core you can deploy without a licence key.
  • Modbus TCP and OPC UA carry most of the data (our production-grade drivers today).
  • You want the plant to run on a small Linux box or a Raspberry Pi.

Pick Ignition when

  • The plant or the client already standardises on Ignition, or the spec names it.
  • You need Siemens S7 or Rockwell EtherNet/IP drivers that are proven on real controllers today. Ours are tested against simulators only (see the README status table).
  • You want a large module catalogue, a training site and a big pool of certified integrators.
  • The project needs a vendor with a long track record more than it needs a low price.

Where each fact comes from.

  1. Inductive Automation docs: Licensing and Activation (trial period) (read 17 November 2026)
  2. Inductive Automation: Ignition price list (read 17 November 2026)
  3. Inductive Automation: Ignition Maker Edition (read 17 November 2026)
  4. Inductive Automation: Ignition pricing (suites, support plans, Edge FAQ) (read 17 November 2026)
  5. Inductive Automation forum: "Ignition comes with its own Java runtime" (read 17 November 2026)
  6. Voltrus SCADA README: features, project status, Core vs Enterprise (read 17 November 2026)
  7. Voltrus SCADA pricing (read 17 November 2026)

Ignition is a trademark of its owner. Voltrus is not affiliated with or endorsed by it.

Tell us about your plant

We reply on WhatsApp or email.

Prefer email? support@voltrus.id